  • 9 September 2023
  • Electrical Switchboard Manufacturer | Technical Articles

AS/NZS 61439.1 – General Rules

AS/NZS 61439.1 is titled “Low-voltage switchgear and controlgear assemblies – Part 1: General rules.” It sets out the universal requirements for low-voltage switchboards and assemblies up to 1,000 V AC or 1,500 V DC.

It doesn’t apply to just one type of switchboard. Instead, it covers them all – main switchboards, distribution boards, motor control centres, and specialised assemblies. The idea is that every other part of the 61439 series (like Part 2 for power switchgear assemblies, Part 3 for distribution boards, etc.) refers back to Part 1 as the baseline.

So if you want to understand what’s really required of a compliant switchboard, you can’t skip Part 1.

Why Was It Introduced?

Before 61439 came along, we used AS/NZS 3439. One of the problems with the old standard was that it divided assemblies into “type-tested” and “partially type-tested.” In practice, this caused confusion and left room for inconsistent interpretations.

AS/NZS 61439.1 cleared all of that up by introducing the concept of design verification. Instead of saying an assembly is or isn’t type-tested, the new system makes sure that every relevant characteristic is either tested, calculated, or otherwise verified.

This gives specifiers and installers much more confidence. No matter which manufacturer builds the switchboard, they know the product has been verified against the same set of rules.

Key Principles in AS/NZS 61439.1

Now, let’s get into the nuts and bolts of what Part 1 actually covers.

1. Clear Definitions and Roles

One of the first things AS/NZS 61439.1 does is clear up terminology. It introduces two important roles:

  • – Original manufacturer – the one who designs and verifies the assembly system.
  • – Assembly manufacturer – the one who puts together the actual switchboard, possibly customising it for a specific project.

This distinction is crucial in practice. For example, a big international manufacturer might design and verify a switchboard system, but a local switchboard builder in Australia assembles it for a particular site. Both have responsibilities under the standard, and AS/NZS 61439.1 makes that clear.

2. General Construction Rules

The standard lays out baseline requirements for switchboard construction. These cover:

  • – Mechanical strength – the switchboard must withstand handling, installation, and service conditions.
  • – Protection against electric shock – assemblies must be built to prevent accidental contact with live parts.
  • – Dielectric properties – insulation and clearance distances must be adequate for the voltage rating.
  • – Temperature rise – components and conductors must not overheat under normal load.
  • – IP rating – the degree of protection against dust and water must be suitable for the environment.

These might sound basic, but they set the minimum expectations across the industry.

3. Design Verification

This is where AS/NZS 61439.1 really sets itself apart. Every assembly characteristic – from short-circuit withstand strength to dielectric properties – must be design verified.

The standard allows three ways of doing this:

  • – Testing – physically testing a representative sample.
  • – Calculation or measurement – using proven formulas or simulations.
  • – Assessment – referencing compliance of individual components.

This flexible approach balances practicality and safety. Not every switchboard needs to be tested from scratch, but every critical property must be proven.

4. Routine Verification

Once a switchboard has been assembled, the job isn’t finished. The assembly manufacturer must carry out routine verification.

This includes things like:

  • – Checking wiring and electrical connections.
  • – Ensuring protective circuits are continuous.
  • – Conducting insulation resistance tests.
  • – Functional testing of devices.

Routine verification ensures that every individual board delivered to site meets the standard – not just the one that was originally tested.

5. Performance Requirements

AS/NZS 61439.1 also lays out the performance characteristics that assemblies must meet. These include:

  • – Withstanding short-circuit currents.
  • – Maintaining protective earth continuity.
  • – Ensuring electromagnetic compatibility (EMC).
  • – Operating safely under rated service conditions.

These requirements give end-users confidence that the switchboard won’t fail when it matters most.

The Australian Context

Here in Australia, AS/NZS 61439 has been gradually replacing AS/NZS 3439. Many projects now specify 61439 compliance as mandatory, especially in commercial and industrial settings.

It also aligns closely with AS/NZS 3000 (the Wiring Rules). For example, AS/NZS 3000 requires that switchboards provide adequate protection against electric shock and fire – AS/NZS 61439.1 provides the detailed framework to make that happen.

By adopting the international IEC 61439 standard and adapting it to local conditions, Australia ensures that our switchboards meet global best practice while also being fit for our environment.

Why It Matters for Specifiers

If you’re a consultant or engineer writing specifications, AS/NZS 61439.1 gives you peace of mind. When you specify that a switchboard must comply with 61439, you know that:

  • – The design has been properly verified.
  • – The assembly will be built to consistent construction rules.
  • – Routine testing will be carried out before delivery.

This reduces the risk of disputes between you, the client, and the switchboard builder. It also makes tendering clearer, because everyone is working from the same baseline.

Why It Matters for Manufacturers

For switchboard builders, AS/NZS 61439.1 sets a clear framework. Yes, it requires more documentation and discipline, but it also levels the playing field.

No longer can one builder cut corners while another goes to the effort of type testing. Everyone must verify their designs and prove compliance. In the long run, this improves industry reputation and reduces the risk of failures.

Challenges in Implementation

Of course, the transition to AS/NZS 61439 hasn’t been without challenges. Some of the main issues manufacturers face include:

  • – The cost of testing and verification.
  • – The need to retrain staff in the new requirements.
  • – Educating clients who may not fully understand what the standard demands.

But despite these hurdles, the benefits outweigh the costs. The standard brings Australian switchboards into line with international best practice and raises the overall safety bar.

We design and manufacture high-quality switchboards. Contact us today to discuss your requirements and get started!

Tags: electrical enclosuresswitchboards
Electrical Switchboard Manufacturer
  • BESS & Batteries
  • Electric Vehicles & EV Charging Switchboards
  • Electrical Enclosures
  • Engineering Resources
  • High & Medium Voltage
  • Integrating Diesel & Backup Generation
  • Power Quality Analysis
  • Protection Relays & Injection Testing
  • Renewable Energy & Power Generation
  • Solar Standards: AS/NZS 4777 2024
  • Switchboards & Components
  • Virtual Power Plants & Smart Grids
  • Wiring Rules AS/NZS 3000
  • electrical switchboard | electrical switchboards
    What is Edge Computing? How it helps power distribution?
    Edge computing refers to an arrangement where data processing occurs… Read more: What is Edge Computing? How it helps power distribution?
  • electrical switchboard | electrical switchboards
    What is Net Zero Building? How it uses Smart Switchboards?
    Net Zero building is designed in a way that allows… Read more: What is Net Zero Building? How it uses Smart Switchboards?
  • electrical switchboard | electrical switchboards
    What is Paralleling Switchgear? How it works?
    Paralleling switchgear is basically a low-voltage switchboard used to control… Read more: What is Paralleling Switchgear? How it works?
  • electrical switchboard | electrical switchboards
    What is Electrification? Understanding the Basics
    Electrification is turning into one of the major trends in… Read more: What is Electrification? Understanding the Basics
  • What is a Data Center?
    What Is a Data Center? Discover How it works!
    DATA CENTER – Each day, we use the internet and… Read more: What Is a Data Center? Discover How it works!
  • 250A Chassis
    Understanding a 250A Chassis in a Distribution Board
    A 250A chassis is an example of a type of… Read more: Understanding a 250A Chassis in a Distribution Board
  • arc flash protection
    Arc Flash Protection – What Really Happens When Systems Fail
    The technician didn’t hear anything unusual. No alarm. No warning.… Read more: Arc Flash Protection – What Really Happens When Systems Fail
  • Do All Switchboards Require a Dedicated Room?
    Do All Switchboards Require a Dedicated Room?
    Switchboards are usually mounted on a garage wall, sometimes in… Read more: Do All Switchboards Require a Dedicated Room?
  • Is SMA leaving the Australian market?
    Why is SMA shutting down in Australia? Explained!
    Is SMA really going to close down? SMA’s move in… Read more: Why is SMA shutting down in Australia? Explained!
  • electrical switchboard | electrical switchboards
    What Are Electronic Overload Relays? Explained!
    Electronic overload relay sends a signal to the contactor to… Read more: What Are Electronic Overload Relays? Explained!
  • electrical switchboard | electrical switchboards
    AS/NZS 3000 Switchboard Rules – Complete Guide for Compliance and Safety
    Switchboard rules is critical for ensuring electrical safety and functionality.… Read more: AS/NZS 3000 Switchboard Rules – Complete Guide for Compliance and Safety
  • electrical switchboard | electrical switchboards
    AS/NZS 3000 Switchboard Clearances: Safety Rules Every Electrician Must Know
    Ensuring proper switchboard clearances is crucial for maintaining safety and… Read more: AS/NZS 3000 Switchboard Clearances: Safety Rules Every Electrician Must Know

Contact Us

Phone: 02 9558 2480

Email: contact@cleantechcontrols.com.au

Sales (VIC) 0435 812 094

Sales (NSW) 0405 352 840

Sales (WA) 0419 423 609

Useful Links

  • Home
  • Electrical Switchboards
  • Injection Testing & PQA
  • Engineering Services
  • Technical Articles
  • About Us
  • Contact Us
© 2020 Clean Technology Controls. All Rights Reserved.