What are Solid-State Circuit Breakers or SSCB?

Circuit breaker protects electrical systems. When there’s a fault—like a short circuit or overload—it disconnects the supply so equipment doesn’t get damaged. Now traditionally, circuit breakers are mechanical. That means they rely on physical movement—contacts opening, springs releasing, arcs forming and being extinguished. And here’s the key point: all of that takes time.

Even if it feels fast, in electrical protection terms, that delay matters. Now imagine if we remove all moving parts completely. That’s exactly what a Solid-State Circuit Breaker, or SSCB, is trying to do.

So what exactly is an SSCB?

Instead of mechanical contacts, SSCBs use power semiconductor devices—like MOSFETs, IGBTs, or silicon carbide devices. So instead of physically separating contacts, what happens is:

The circuit is interrupted electronically.

It’s basically a controlled “electronic OFF” of the current path. No moving parts. No mechanical delay. No arc in the traditional sense. And because electronics operate extremely fast, we’re talking about interruption in the microsecond range. That alone already puts SSCBs in a completely different category compared to traditional breakers.

Why is this becoming important now?

Modern electrical networks are changing. We are no longer dealing with simple AC-only systems.

We now have:

  • • Solar PV systems
  • • Battery energy storage systems
  • • EV fast charging infrastructure
  • • DC microgrids
  • • Data centers with high reliability requirements

And most of these systems are either DC or heavily power-electronics based. Now here’s the challenge with DC systems. There is no natural current zero crossing. In AC systems, every cycle naturally passes through zero current, which helps extinguish arcs. But in DC systems, current flows continuously. So when a fault occurs, the energy keeps feeding into the fault. That makes interruption much more difficult using mechanical devices. And this is exactly where SSCBs become very relevant.

How does an SSCB actually operate?

Let’s break it down like a real event happening inside the system.

Step 1: Continuous monitoring

First, the system is constantly measuring current and voltage using high-speed sensors.

So in Step 1, which is continuous monitoring, the idea is simple: the SSCB is always measuring the electrical current in real time.

Inside the device, there’s a current sensor that constantly feeds signal data to a control circuit. This isn’t something that happens every now and then—it’s continuous sampling of the current waveform.

The key thing here is that the SSCB is not waiting for a mechanical trigger or a thermal buildup. It is always reading the instantaneous current value and sending that information to a digital controller.

Now depending on the design, that controller could be a DSP or FPGA, but the main job is the same—it processes the sensor signal as it comes in and keeps track of what the current is doing at every moment.

So instead of reacting after a delay, the system already has a real-time picture of the current flowing through the breaker.

That’s basically what continuous monitoring means in SSCBs: constant sensing, constant data input, and real-time processing of the electrical current.

Step 2: Fault detection

When something abnormal happens—like a sudden current spike—the protection system evaluates it. This is not thermal or mechanical detection. This is digital logic. It can include:

  • • Overcurrent detection
  • • Rate-of-rise of current (di/dt protection)
  • • Short-circuit identification
  • • Transient filtering to avoid false trips

So the system is basically deciding in real time whether the event is a real fault or just a normal transient condition.

So after continuous monitoring, the next thing the SSCB does is fault detection.

Now this is important—you don’t just treat every current spike as a fault. In real systems, the controller first compares what it’s seeing with expected operating conditions.

So the first thing it looks at is the current level. If it goes beyond a certain limit, that already raises a flag. But that alone is not enough.

Because in real electrical systems, you can have normal events that look like spikes. For example, when a motor starts or when a capacitor bank is energized, you can get a sudden increase in current. So if the breaker reacts to that immediately, it would cause nuisance tripping.

That’s why SSCBs don’t rely on current magnitude alone.

They also look at how fast the current is rising. This is the di/dt value, or the rate of change of current. In real faults, especially in DC systems, the current rises very quickly compared to normal load behavior. So a very steep rise is a strong indicator that something is wrong.

At the same time, the controller also considers how the voltage is behaving. In many fault cases, you don’t just see current going up—you also see voltage dropping at the same time. That combination gives a clearer picture that it’s not just a normal transient.

Now all of this is being processed in real time inside the control system. The SSCB is not making a decision based on a single sample. It’s continuously evaluating a short window of data to make sure the condition is really persistent and not just a brief disturbance.

So in simple terms, fault detection in an SSCB is basically a decision process. The system is checking: is this just a normal operating event, or is this a real fault that needs immediate interruption?

Once the system is confident that it’s a fault, that’s the only time it moves to the next step, which is the actual electronic switching off.

Step 3: Electronic interruption

Once a fault is confirmed, the gate signals of the semiconductor devices are turned off.

This is the core of SSCB operation.

  • • MOSFETs turn off extremely fast
  • • IGBTs turn off slightly slower due to carrier dynamics
  • • Thyristors require additional commutation techniques

But in all cases, the key idea is the same:

The current path is interrupted electronically instead of mechanically.

This is where SSCBs achieve microsecond-level response.

Step 4: Energy absorption

Now here’s something very important that often gets overlooked. Just turning off the switch does not mean the energy disappears. Because electrical systems contain inductance, and inductors resist sudden changes in current. So the stored energy must go somewhere:

This equation represents the energy stored in an inductor. So when you have inductance in a system—which is basically present in cables, motors, transformers, and almost all real power systems—energy is stored in the magnetic field whenever current is flowing.

One important thing to notice here is that the energy depends on the square of the current. So if the current increases, the stored energy increases very quickly.

Now here’s what happens during interruption.

When the SSCB suddenly turns off the current using semiconductor devices, the current cannot just drop instantly in an inductive circuit. The inductor resists that sudden change. Because of that, the stored energy has to be released somewhere.

And that is exactly why this formula is important—it tells us how much energy the system needs to handle after the turn-off event.

During this process, the stored energy is released and can create a high voltage spike. If it is not properly controlled, that spike can damage the semiconductor devices inside the SSCB.

This is why SSCBs need additional protection components such as MOVs, snubber circuits, or active clamping circuits. Their role is to safely absorb or control that energy so the switching devices are not overstressed.

So in simple terms, this formula is there to show one key idea:

the higher the current at the moment of interruption, the higher the energy that the SSCB must safely manage.

That energy is released during interruption and can create dangerous voltage spikes. To manage this, SSCBs use energy absorption methods such as:

  • • MOV clamps
  • • RC snubber circuits
  • • Capacitor-based energy buffers

Without these, the semiconductor devices would be destroyed by overvoltage stress.

How fast is it really?

Traditional mechanical circuit breakers operate in the millisecond range. SSCBs operate in the microsecond range. Some research prototypes have demonstrated interruption times below 50 microseconds under controlled conditions. That’s not just an improvement in speed—that’s a completely different operational time domain.

But is it perfect? Not really.

Like any engineering solution, SSCBs come with trade-offs.

1. Thermal losses

Even when fully ON, semiconductor devices still have conduction losses. That means continuous heat generation. So thermal management becomes a major design requirement—sometimes even requiring advanced cooling systems.

2. Cost

Right now, SSCBs are significantly more expensive than mechanical breakers because they involve:

  • • High-performance semiconductors
  • • Fast digital control systems
  • • Complex protection algorithms
  • • Thermal management systems
3. System complexity

This is not a standalone mechanical device. This is a full electronic system. It includes:

  • • Sensors
  • • DSP or FPGA-based controllers
  • • Gate driver circuits
  • • Protection logic firmware

So from an engineering perspective, it’s a lot more complex to design and maintain.

Where are SSCBs used today?

SSCBs are not replacing every breaker yet. Instead, they are used in high-performance applications where speed is critical:

  • • DC shipboard electrical systems
  • • Renewable energy microgrids
  • • Battery energy storage systems
  • • EV fast charging stations
  • • Aerospace and defense power systems

In these environments, fast fault isolation is not optional—it is essential.

Where is this technology heading?

The industry is not moving toward a full replacement of mechanical breakers just yet. Instead, the realistic direction is hybrid systems. That means:

  • • Mechanical switching handles normal current conduction
  • • Solid-State Circuit Breakers handle fast fault interruption

This gives you the best of both worlds—efficiency and speed. On top of that, wide-bandgap semiconductors like Silicon Carbide (SiC) are making SSCBs more practical by improving:

  • • Efficiency
  • • Thermal performance
  • • Voltage handling capability

So the technology is clearly moving toward more practical, scalable designs.

If you step back and look at SSCBs from a systems point of view, this is not just a faster circuit breaker.

It’s a shift in protection philosophy—from mechanical interruption to fully electronic, software-assisted fault control. And that shift becomes necessary because modern electrical systems are no longer simple passive networks. They are dynamic, power-electronics-driven systems. So in many ways, SSCBs are not just an upgrade. They are part of the evolution of how we protect electrical infrastructure.

We design and manufacture high-quality switchboards. Contact us today to discuss your requirements and get started!

Tags: protection relays
Electrical Switchboard Manufacturer
  • BESS & Batteries
  • Electric Vehicles & EV Charging Switchboards
  • Electrical Enclosures
  • Engineering Resources
  • High & Medium Voltage
  • Integrating Diesel & Backup Generation
  • Power Quality Analysis
  • Protection Relays & Injection Testing
  • Renewable Energy & Power Generation
  • Solar Standards: AS/NZS 4777 2024
  • Switchboards & Components
  • Virtual Power Plants & Smart Grids
  • Wiring Rules AS/NZS 3000
  • electrical switchboard | electrical switchboards
    What is Edge Computing? How it helps power distribution?
    Edge computing refers to an arrangement where data processing occurs… Read more: What is Edge Computing? How it helps power distribution?
  • electrical switchboard | electrical switchboards
    What is Net Zero Building? How it uses Smart Switchboards?
    Net Zero building is designed in a way that allows… Read more: What is Net Zero Building? How it uses Smart Switchboards?
  • electrical switchboard | electrical switchboards
    What is Paralleling Switchgear? How it works?
    Paralleling switchgear is basically a low-voltage switchboard used to control… Read more: What is Paralleling Switchgear? How it works?
  • electrical switchboard | electrical switchboards
    What is Electrification? Understanding the Basics
    Electrification is turning into one of the major trends in… Read more: What is Electrification? Understanding the Basics
  • What is a Data Center?
    What Is a Data Center? Discover How it works!
    DATA CENTER – Each day, we use the internet and… Read more: What Is a Data Center? Discover How it works!
  • 250A Chassis
    Understanding a 250A Chassis in a Distribution Board
    A 250A chassis is an example of a type of… Read more: Understanding a 250A Chassis in a Distribution Board
  • arc flash protection
    Arc Flash Protection – What Really Happens When Systems Fail
    The technician didn’t hear anything unusual. No alarm. No warning.… Read more: Arc Flash Protection – What Really Happens When Systems Fail
  • Do All Switchboards Require a Dedicated Room?
    Do All Switchboards Require a Dedicated Room?
    Switchboards are usually mounted on a garage wall, sometimes in… Read more: Do All Switchboards Require a Dedicated Room?
  • Is SMA leaving the Australian market?
    Why is SMA shutting down in Australia? Explained!
    Is SMA really going to close down? SMA’s move in… Read more: Why is SMA shutting down in Australia? Explained!
  • electrical switchboard | electrical switchboards
    What Are Electronic Overload Relays? Explained!
    Electronic overload relay sends a signal to the contactor to… Read more: What Are Electronic Overload Relays? Explained!
  • electrical switchboard | electrical switchboards
    AS/NZS 3000 Switchboard Rules – Complete Guide for Compliance and Safety
    Switchboard rules is critical for ensuring electrical safety and functionality.… Read more: AS/NZS 3000 Switchboard Rules – Complete Guide for Compliance and Safety
  • electrical switchboard | electrical switchboards
    AS/NZS 3000 Switchboard Clearances: Safety Rules Every Electrician Must Know
    Ensuring proper switchboard clearances is crucial for maintaining safety and… Read more: AS/NZS 3000 Switchboard Clearances: Safety Rules Every Electrician Must Know

Contact Us

Phone: 02 9558 2480

Email: contact@cleantechcontrols.com.au

Sales (VIC) 0435 812 094

Sales (NSW) 0405 352 840

Sales (WA) 0419 423 609

Useful Links

  • Home
  • Electrical Switchboards
  • Injection Testing & PQA
  • Engineering Services
  • Technical Articles
  • About Us
  • Contact Us
© 2020 Clean Technology Controls. All Rights Reserved.