In Australia, the majority of distribution infrastructure sits in the 11–33 kV band. The 11 kV level is extremely common in older urban networks and still appears widely in commercial precincts, industrial estates and suburban distribution systems. The 22 kV level is prominent in states like Victoria and increasingly in NSW and parts of WA, particularly in newer or higher-capacity distribution corridors. When you step up to 33 kV, you tend to find it at zone substations, in collector circuits for renewables, at large industrial facilities or along extensive rural feeders.
These voltage levels strike a balance between efficiency, safety, equipment size and cost, which is why network service providers such as Ausgrid, Energex, Essential Energy, SA Power Networks, Horizon Power and TasNetworks all rely heavily on them. They’re high enough to minimise losses over distance and support large loads, yet still low enough to allow equipment to be compact, manageable and cost-effective.
Switchgear Types Used Across Australian Installations
Although switchgear varies from manufacturer to manufacturer, most of what you encounter in Australia falls into a few familiar categories. The first is the Ring Main Unit, or RMU, which is particularly common at 11 kV and 22 kV. If you’ve ever inspected a kiosk substation in an urban street or commercial site, there’s a strong chance the medium-voltage component inside was an RMU. These units are compact, sealed, factory-assembled systems designed for reliability and minimal maintenance. RMUs usually include load break switches, earthing switches, vacuum circuit breaker modules and cable termination compartments. They’re a natural fit for ring or loop networks common in urban distribution because they provide high reliability through alternative supply paths. They also work exceptionally well as the HV interface feeding pad-mount transformers.
The next major category is metal-clad and metal-enclosed switchgear. This is the classic “big iron” of medium-voltage distribution. Unlike RMUs, which are compact and simplified, metal-clad switchgear is modular, customisable and built to handle high fault levels and complex protection schemes. The design is based on fully segregated compartments for the busbars, circuit breakers and cable terminations, helping to improve safety and maintainability. Withdrawable vacuum circuit-breakers are standard, making it easy to isolate equipment for testing or replacement. You tend to see metal-clad gear in zone substations, mining operations, data centres, hospitals, industrial plants and renewable energy hubs. At 33 kV, metal-clad switchgear is almost always the preferred option because of its robustness and configurable layout.
Gas-Insulated Switchgear, or GIS, is another increasingly common solution in Australia, particularly where space or environmental conditions are challenging. Unlike AIS or metal-clad designs, GIS houses all primary components inside sealed metal enclosures filled with insulating gas. Traditionally this gas was SF₆, which offers exceptional dielectric performance but comes with a high global warming potential. Many Australian organisations are now pushing toward reduced SF₆ usage, creating interest in low-GWP alternatives. GIS earns its keep in coastal locations, mining environments, tunnels, high-density city substations, offshore facilities and anywhere dust, humidity, corrosion or space constraints make AIS or metal-clad gear impractical. GIS installations often last decades with minimal intervention, which is a significant advantage in remote or high-risk environments.
Air-Insulated Switchgear, or AIS, is the simplest and most spacious approach. While it requires more physical room than GIS or RMUs, it’s cost-effective and easy to inspect and maintain. AIS remains popular in rural substations, large indoor switchrooms and other locations where footprint isn’t a problem.
Control and Protection — The Intelligence Behind the Switchgear
Modern MV switchgear is far more than a set of breakers and busbars. The real “intelligence” sits in the control and protection system. Protection relays, or IEDs, have advanced dramatically over the last decade. Today’s relays are microprocessor-based devices that handle overcurrent and earth-fault protection, directional protection for networked feeders, transformer differential protection, distance protection for longer 33 kV lines and breaker-failure backup schemes. Many sites now also use arc-flash detection systems, combining optical sensors with fast logic to clear internal faults in milliseconds.
In Australia, utilities and large industrial operators increasingly expect relays to support advanced diagnostics, breaker health monitoring, disturbance recording, event logs and cybersecure communication. Brands such as ABB, Siemens, Schneider, SEL and NHP/GE are common across Australian installations. Relays now routinely interface with SCADA through protocols like IEC 61850, DNP3 and, in some cases, IEC 60870-5-104. IEC 61850 is particularly influential because it standardises data structures and enables high-speed GOOSE messaging for protection schemes. Some newer Australian installations are moving toward digital substations, where conventional copper signalling is replaced by Ethernet-based messaging.
SCADA integration is no longer a luxury; it’s an essential part of ensuring reliability and fast fault response. Operators depend on remote monitoring for breaker positions, load levels, transformer status, protection events and alarms. Remote control also allows faster outage restoration, which is critical for utilities under pressure to improve network reliability metrics.
Another key component of control and protection is internal arc safety. Australian installations take internal arc classification seriously, usually following IEC 62271-200 requirements. Many metal-clad and GIS systems incorporate arc ducts, pressure relief mechanisms, optical sensors and rapid earthing switches to protect personnel and limit equipment damage. As expectations around worker safety grow, arc-flash mitigation is becoming one of the most important considerations in switchgear selection.
Metering also plays a major role. Most medium-voltage installations use dedicated protection-class and metering-class CTs and VTs, along with power quality meters and, where required by DNSPs, revenue-grade metering. HV customers who take supply directly at 11 or 22 kV rely on these meters for billing, power factor tracking and network compliance reporting.
Common Installation Formats in Australia
In Australia, packaged substations — often called kiosks — are extremely popular because they streamline installation and reduce on-site construction complexity. A kiosk typically includes an RMU or compact GIS section on the MV side, a transformer in the centre, and an LV distribution board on the opposite end. Everything is factory assembled, tested and delivered as a single unit, which is particularly attractive for developers, utilities and industrial sites with tight build schedules. These kiosks are standard for 11 kV and 22 kV networks and are rated for transformers typically between 500 kVA and 2.5 MVA.
Another common format is the dedicated indoor MV switchroom, used extensively in high-rise developments, commercial buildings, industrial plants and data centres. These rooms house metal-clad switchgear and often include fire-rated construction, cable trenches or rising mains, and isolated control or relay rooms. The focus in these facilities is long-term maintainability, fault-level flexibility and safety.
For remote locations, especially in mining, construction and rural utility projects, containerised substations are increasingly common. These prefabricated units can include 11 kV or 33 kV switchgear, SCADA systems, auxiliary power systems and even transformers in a transportable enclosure. They’re ideal for rapid deployment, temporary networks, isolated microgrids and sites requiring relocatable infrastructure.
Insulation Technologies and Environmental Considerations
Insulation medium is an important consideration when selecting switchgear. SF₆ has historically been the dominant gas for GIS and some RMUs because of its excellent dielectric strength and arc-quenching properties. However, its extremely high global warming potential means operators in Australia are gradually transitioning toward alternatives. Although SF₆-free technology is still maturing at medium-voltage levels, products using fluoroketone-based mixtures, dry air or hybrid insulation systems are becoming more common. Many utilities now specify low-GWP options for new installations wherever possible.
Vacuum interruption remains the standard for circuit breakers across 11–33 kV. Vacuum interrupters offer long service life, excellent switching performance and very little maintenance compared to older oil-filled or air-blast designs. Their reliability is one of the reasons MV switchgear has become safer and more dependable over the last two decades.
Digitalisation and the Future of MV Switchgear in Australia
One of the biggest shifts happening right now is the move toward digital MV networks. This includes wider adoption of IEC 61850, increasing use of fully digital protection schemes, greater reliance on SCADA, and integration of switchgear into broader asset management platforms. Condition monitoring is becoming standard, with sensors tracking breaker operations, partial discharge, temperature, humidity and cable health. Utilities and industrial operators increasingly use this data to move from time-based to predictive maintenance.
Another key trend is the rise of DER — especially solar, wind and battery energy storage — which places new demands on MV switchgear. With more bidirectional power flow, more embedded generation and more complex fault characteristics, protection schemes need to be more adaptable. Directional earth-fault protection, advanced feeder automation and dynamic settings are becoming more commonplace. These changes are particularly noticeable in states like South Australia, where renewable penetration is high and network stability is critical.
Environmental expectations are also influencing design decisions. There is growing pressure to eliminate or limit SF₆, improve end-of-life recyclability and minimise embodied carbon in switchgear manufacturing. Manufacturers are responding with modular designs, low-GWP gases, digital monitoring and extended equipment lifespans.
We design and manufacture high-quality switchboards. Contact us today to discuss your requirements and get started!