CT Accuracy Class – Why does it matter?

When you look at the nameplate of a current transformer, one of the most important things you’ll see is the ct accuracy class. At first glance, it might look like just a number—something like 0.5, 1.0, or maybe 5P10—but this small label actually tells you a lot about how the CT will behave.

In simple terms, the accuracy class defines how accurate the CT is under specific conditions. It tells you how closely the secondary current matches the primary current once it has been scaled down by the ratio.

No CT is perfectly accurate. There will always be some error due to losses in the core, winding resistance, and magnetic effects. The accuracy class gives you a limit for that error so you know what to expect.

How is CT accuracy expressed?

For metering CTs, accuracy is usually expressed as a simple number like 0.2, 0.5, or 1.0.

This number represents the percentage error at rated conditions. For example, a class 0.5 CT means the error should not exceed 0.5 percent when the CT is operating at its rated current and burden.

So if your system is running at a certain current, a class 0.5 CT will give you a reading that is very close to the true value, with only a small allowable deviation.

For protection CTs, the format is different. You might see something like 5P10 or 10P20. This includes both an accuracy class and an accuracy limit factor, which tells you how the CT performs under fault conditions.

What is the difference between metering and protection accuracy classes?

This is where things start to get more interesting.

Metering CTs are designed for accuracy during normal operating conditions. Their job is to provide precise measurements for energy monitoring, billing, and system analysis. That’s why they have low error limits, such as 0.5 or even 0.2.

Protection CTs, on the other hand, are not primarily focused on small errors at normal current levels. Instead, their priority is to remain accurate during high fault currents so that protection relays can operate correctly.

That’s why protection CTs use designations like 5P or 10P. The number represents the allowable percentage error under specified fault conditions, and the additional number (like 10 or 20) represents the accuracy limit factor.

So while metering CTs focus on precision at normal loads, protection CTs focus on reliability during abnormal conditions.

What does something like 5P10 actually mean?

Let’s break that down in a simple way.

The “5P” part means the CT has a composite error of up to 5 percent under specified conditions. This is acceptable for protection purposes, where exact precision is less important than consistent and predictable behaviour.

The “10” refers to the accuracy limit factor, or ALF. This means the CT can handle up to 10 times its rated current while still maintaining its specified accuracy.

So a 5P10 CT will remain reasonably accurate even when the current rises to ten times its rated value. Beyond that, it may begin to saturate and lose accuracy.

This is exactly what you want in protection systems. The CT must remain reliable during faults so that relays can detect and isolate the issue.

How does burden affect CT accuracy?

Burden plays a huge role in accuracy, and it’s something that cannot be ignored.

Every CT is designed to operate within a specified burden. When the actual burden matches the rated burden, the CT performs as expected and meets its accuracy class.

If the burden increases beyond the rated value, the CT has to work harder to drive the secondary current. This increases errors and can push the CT closer to saturation.

On the other hand, if the burden is significantly lower than the rated burden, the CT may also experience increased error, particularly in metering applications.

This is why accuracy class is always specified along with a rated burden. The two go hand in hand.

What is phase error and why does it matter?

Accuracy isn’t just about magnitude—it’s also about timing.

In AC systems, current is constantly changing direction, forming a waveform. Ideally, the secondary current produced by the CT should be perfectly in phase with the primary current.

However, due to the characteristics of the CT, there is often a small phase shift between the primary and secondary currents. This is called phase error.

For basic current measurement, this might not seem like a big deal. But in power and energy calculations, phase error can significantly affect results, especially when calculating power factor or real power.

Higher accuracy class CTs are designed to minimise both magnitude error and phase error, which is why they are used in precise metering applications.

Why does accuracy class matter so much in real systems?

It’s easy to overlook accuracy class, especially if everything seems to be working fine. But over time, even small errors can add up.

In billing applications, inaccurate measurements can lead to incorrect energy charges. In monitoring systems, poor accuracy can result in misleading data, making it harder to analyse system performance.

In protection systems, the consequences can be even more serious. If the CT does not provide reliable current information during a fault, the protection system may not operate as intended.

So accuracy class is not just a technical detail—it directly affects system performance, reliability, and even cost.

Can you use a higher accuracy class “just to be safe”?

This is a common question, and the answer is not always straightforward.

Using a higher accuracy class, such as 0.2 instead of 0.5, can improve measurement precision. However, it also comes with higher cost and may not be necessary for all applications.

More importantly, accuracy class alone does not guarantee better performance if other factors, such as burden and installation, are not properly managed.

So while it might be tempting to choose the highest accuracy available, the better approach is to match the accuracy class to the actual requirements of the system.

How do you choose the right accuracy class?

Choosing the right accuracy class starts with understanding the application.

For general monitoring, a class 1.0 CT may be sufficient. For more precise measurements, such as energy billing or detailed analysis, a class 0.5 or 0.2 CT is more appropriate.

For protection systems, you need to look at protection classes like 5P or 10P, along with the required accuracy limit factor.

You also need to consider how the CT will be used in combination with other equipment. The overall system accuracy depends on more than just the CT.

How does accuracy class connect with burden, saturation, and ISF?

By now, you can probably see how everything ties together.

Accuracy class defines how precise the CT is under certain conditions. Burden affects how hard the CT has to work, which in turn affects accuracy.

Saturation determines what happens when the CT is pushed beyond its limits. ISF controls how saturation is used to protect instruments in metering applications.

All of these factors are interconnected. You can’t look at one in isolation.

For example, even a high-accuracy CT will perform poorly if the burden is incorrect. And a CT with the right accuracy class but the wrong saturation characteristics may not behave as expected during faults.

We design and manufacture high-quality switchboards. Contact us today to discuss your requirements and get started!

Tags: switchboards
Electrical Switchboard Manufacturer
  • BESS & Batteries
  • Electric Vehicles & EV Charging Switchboards
  • Electrical Enclosures
  • Engineering Resources
  • High & Medium Voltage
  • Integrating Diesel & Backup Generation
  • Power Quality Analysis
  • Protection Relays & Injection Testing
  • Renewable Energy & Power Generation
  • Solar Standards: AS/NZS 4777 2024
  • Switchboards & Components
  • Virtual Power Plants & Smart Grids
  • Wiring Rules AS/NZS 3000
  • electrical switchboard | electrical switchboards
    What is Edge Computing? How it helps power distribution?
    Edge computing refers to an arrangement where data processing occurs… Read more: What is Edge Computing? How it helps power distribution?
  • electrical switchboard | electrical switchboards
    What is Net Zero Building? How it uses Smart Switchboards?
    Net Zero building is designed in a way that allows… Read more: What is Net Zero Building? How it uses Smart Switchboards?
  • electrical switchboard | electrical switchboards
    What is Paralleling Switchgear? How it works?
    Paralleling switchgear is basically a low-voltage switchboard used to control… Read more: What is Paralleling Switchgear? How it works?
  • electrical switchboard | electrical switchboards
    What is Electrification? Understanding the Basics
    Electrification is turning into one of the major trends in… Read more: What is Electrification? Understanding the Basics
  • What is a Data Center?
    What Is a Data Center? Discover How it works!
    DATA CENTER – Each day, we use the internet and… Read more: What Is a Data Center? Discover How it works!
  • 250A Chassis
    Understanding a 250A Chassis in a Distribution Board
    A 250A chassis is an example of a type of… Read more: Understanding a 250A Chassis in a Distribution Board
  • arc flash protection
    Arc Flash Protection – What Really Happens When Systems Fail
    The technician didn’t hear anything unusual. No alarm. No warning.… Read more: Arc Flash Protection – What Really Happens When Systems Fail
  • Do All Switchboards Require a Dedicated Room?
    Do All Switchboards Require a Dedicated Room?
    Switchboards are usually mounted on a garage wall, sometimes in… Read more: Do All Switchboards Require a Dedicated Room?
  • Is SMA leaving the Australian market?
    Why is SMA shutting down in Australia? Explained!
    Is SMA really going to close down? SMA’s move in… Read more: Why is SMA shutting down in Australia? Explained!
  • electrical switchboard | electrical switchboards
    What Are Electronic Overload Relays? Explained!
    Electronic overload relay sends a signal to the contactor to… Read more: What Are Electronic Overload Relays? Explained!
  • electrical switchboard | electrical switchboards
    AS/NZS 3000 Switchboard Rules – Complete Guide for Compliance and Safety
    Switchboard rules is critical for ensuring electrical safety and functionality.… Read more: AS/NZS 3000 Switchboard Rules – Complete Guide for Compliance and Safety
  • electrical switchboard | electrical switchboards
    AS/NZS 3000 Switchboard Clearances: Safety Rules Every Electrician Must Know
    Ensuring proper switchboard clearances is crucial for maintaining safety and… Read more: AS/NZS 3000 Switchboard Clearances: Safety Rules Every Electrician Must Know

Contact Us

Phone: 02 9558 2480

Email: contact@cleantechcontrols.com.au

Sales (VIC) 0435 812 094

Sales (NSW) 0405 352 840

Sales (WA) 0419 423 609

Useful Links

  • Home
  • Electrical Switchboards
  • Injection Testing & PQA
  • Engineering Services
  • Technical Articles
  • About Us
  • Contact Us
© 2020 Clean Technology Controls. All Rights Reserved.